Aquablend 2000 - 3-Hole Lockable Stainless Steel Cabinet

Aquablend's technology provides superior control, under changing pressure and temperature conditions and at ambient start up when scald protection is needed most. Aquablend 2000 has a polished chrome plated finish and is NSW Health Care approved. Anti-tamper, lockable stainless steel box for easier installation and servicing. The durable box has a brushed stainless cover plate and includes TMV mounted on support bracket, fully plumbed with test port on outlet. Recessed model with oversized fascia and adjustable depth to allow for various wall types.

Key features

  • Australian design and manufacture and Standards Licensed to AS4032.1
  • Scald and thermal shock protection with rapid thermal shut-off should either the cold or hot water supply failure
  • Highly responsive mixed temperature control (+/- 2 Degrees Celcius) under changing inlet temperature and pressure conditions
  • Delivers excellent flow, operating at a minimum pressure of 20kPa
  • Supplied complete with TMV mounted on support bracket, fully plumbed with test port on outlet
  • Access panel is removable for easy access especially in small spaces or near walls - Hinged door option available
  • Products

    Order code Aquablend 2000 - 3-Hole Lockable Stainless Steel Cabinet
    ATMS216E
    Exposed Box and Removable Lid
    ATMS216R
    Recessed Box and Removable Lid
    ATMS216RS
    Recessed Box and Removable Lid with Security Torx Screws
  • Temperature Adjustment Range 38 to 50C
    Dynamic Inlet Pressures 20kPa Min - 500kPa Max
    Static Inlet Pressure 1600kPa Max
    Flow Rates 38lpm@300kPa pressure loss
    Minimum Flow Rate for stable outlet temperature 4 litres/min
    Inlet size 1/2" MI comp (ATM711) or 3/4"FI (ATM713)
    Outlet size 3/4" BSP MI
    Inlet Temperatures Cold Supply: Min 5 C Max 30 C Hot Supply: Min 55 C Max 90 C
    For optimum operation it is recommended that the hot and cold water supply pressures be balanced within +/- 10%. Hot to Mix temperature differential required for stable operation is minimum 10?C. * Enware products are to be installed in accordance with the Plumbing Code of Australia and AS/NZS3500. NOTE: Enware Australia advises: 1. Due to ongoing Research and Development, specifications may change without notice. 2. Component specifications may change on some export models.