• ATM710.jpg

Aquablend 1000 Thermostatic Mixing Valve

Aquablend's technology provides superior control, under changing pressure and temperature conditions as well as at ambient start up when scald protection is needed most. The proven performance, reliability and low 'whole of life' cost makes Aquablend a popular choice with specifiers, engineers, plumbers and property owners. The Aquablend 1000 is engineered for a maximum temperature of 50 Degrees Celsius to also accommodate residential applications. (Note for NSW Health applications refer to Aquablend 1500 or 2000 models)

Key features

  • Australian design and manufacture and Standards Licensed to AS4032.1
  • Scald and thermal shock protection with rapid thermal shut-off should either the cold or hot water supply failure
  • Highly responsive mixed temperature control (+/- 2 Degrees Celcius) under changing inlet temperature and pressure conditions
  • Delivers excellent flow, operating at a minimum pressure of 20kPa
  • Supplied complete with isolating valves, non-returns and dual stage strainers incorporating temperature/pressure test ports
  • Flexible installation - inlet and outlet connections may be rotated to suit pipework design
  • Products

    Order code Aquablend 1000 Thermostatic Mixing Valve
    ATM710
    15mm MI Inlet 20mm MI Outlet with 15mm Adaptor
  • Temperature Adjustment Range 38 to 50C
    Dynamic Inlet Pressures 20kPa Min - 500kPa Max
    Static Inlet Pressure 1600kPa Max
    Flow Rates 39lpm@300kPa pressure loss
    Minimum Flow Rate for stable outlet temperature 4 litres/min (4lpm is recommended for optimum performance)
    Inlet size 1/2" compression nuts
    Outlet size 1" complete with 1"x1/2" & 1"x 3/4" BSP adaptors
    Inlet Temperatures Cold Supply: Min 5 C Max 30 C Hot Supply: Min 55 C Max 90 C
    For optimum operation it is recommended that the hot and cold water supply pressures be balanced within +/- 10% Hot to Mix temperature differential required for stable operation is minimum 10 C. * Enware products are to be installed in accordance with the Plumbing Code of Australia and AS/NZS3500. NOTE: Enware Australia advises: 1. Due to ongoing Research and Development, specifications may change without notice. 2. Component specifications may change on some export models.
  • ATM710 Line Drawing
  • Document type File type
    Brochure Aquablend TMV's I Aquablend - Product Guide
    Installation guide pdf
    PDF Dimensional Drawings ATM710
Email Us